Pass-through junction box type 07-5105
Pass-through junction boxes type 07-5105-****/**** and 07-5105-****/****S are intended for connection of intrinsically safe ia/ib and optical op is communications systems, data transmission systems, control systems, video surveillance equipment, sensors etc. The boxes are used for connection and branching of cables and wires with the use of certified connection terminals. The enclosure type 07-5105-****/**** is made of black polyester reinforced with fibreglass, and the enclosure 5105-****/****S is made of stainless steel. All enclosures are Ex e rated.
Characteristics
- connecting and branching of power, control and signal cables and conductors,
- connecting lighting systems, devices or sensors,
- can be used in intrinsically safe circuits,
- polyester enclosure providing mechanical strength of 7 Nm,
- special lid closure thanks to use of captive screws,
- protection rating, at least IP 65.

Explosion protection
Marking
I M1 Ex ia I Ma
I M1 Ex ia op is I Ma
II 1G Ex ia IIC TX Ga
II 1G Ex ia op is IIC TX Db
II 2D Ex ia IIIC TX Db
II 2D Ex ia op is IIIC TX Db
PO Exial
Ambient temperature
-20°C..+40°C,-55°C..+40°C, -55°C..+55°C
Certificate
OBAC 05 ATEX 008
TC BY/112 02.01. 103,00176
Rated values
Ingress protection rating
IP65/IP66
The minimum wire cross-section
10 mm2
Selection table | |||||||
Execution | Tag | Dimensions | Tag | Number of terminals | Terminal type | Tag | Number of PE terminals |
Ex i | 05 | 80x75x55 | 0800/7555 | Enter a number | Clamp
UK 2.5 Phoenix (2.5 mm2) |
2.5 | Specify
number |
110x75x55 | 1100/7555 | ||||||
160x75x55 | 1600/7555 | ||||||
190x75x55 | 1900/7555 | ||||||
122x120x120 | 1221/2090 | Clamp
UK 4 Phoenix (4 mm2) |
4 | ||||
220x120x90 | 1221/2012 | ||||||
160x160x90 | 2201/2090 | ||||||
160x160x120 | 1601/6012 | ||||||
260x160x90 | 2601/6090 | ||||||
360x160x90 | 3601/6090 | Clamp
UK 6 Phoenix (6 mm2) |
6 | ||||
560x160x90 | 5601/6090 | ||||||
200x250x120 | 2002/5012 | ||||||
255x250x120 | 2552/5012 | ||||||
255x250x160 | 2552/2016 | ||||||
400x250x120 | 4002/5012 | Clamp
UK 10 Phoenix (10 mm2) |
10 | ||||
400x250x160 | 4002/5016 | ||||||
400x405x120 | 4004/0512 | ||||||
400x405x160 | 4004/0516 | ||||||
600x250x120 | 6002/0512 |
Code: 07-51
The following table shows the maximum number of cable outputs that can be mounted on the box wall.
Box IP 07-5178-…./….
Box Ex i 07-5105-…./….
The way of marking the sides of the box
& nbsp; |
|||||||||||
Catalog # | wall | M 12×1.5
(2-6 mm) |
M 16×1.5
(4-8 mm) |
M 16×1.5
(5-10 mm) |
M 20×1.5
(6.5-12 mm) |
M 20×1.5
(10-14 mm) |
M 25×1.5
(13-18 mm) |
M 32×1.5
(18-25 mm) |
M 40×1.5
(22-32 mm) |
M 50×1.5
(32-38 mm) |
M 63×1.5
(37-44 mm) |
07 -____- 0800/7555 | A / B
C / D |
4
1 |
2
1 |
2
– |
2
– |
1
– |
1
– |
–
– |
–
– |
–
– |
–
– |
07 -____- 1100/7555 | A / B
C / D |
6
1 |
4
1 |
3
– |
3
– |
2
– |
2
– |
–
– |
–
– |
–
– |
–
– |
07 -____- 1600/7555 | A / B
C / D |
12
1 |
6
1 |
5
– |
4
– |
4
– |
3
– |
–
– |
–
– |
–
– |
–
– |
07 -____- 1900/7555 | A / B
C / D |
15
1 |
8
1 |
6
– |
5
– |
5
– |
4
– |
–
– |
–
– |
–
– |
–
– |
07 -____- 1221/2090 | A / B
C / D |
13
4 |
9
4 |
5
2 |
5
2 |
4
2 |
3
1 |
2
1 |
1
1 |
1
– |
–
– |
07 -____- 1221/2012 | A / B
C / D |
13
4 |
9
4 |
5
2 |
5
2 |
4
2 |
3
1 |
2
1 |
1
1 |
1
– |
–
– |
07 -____- 2201/2090 | A / B
C / D |
28
4 |
18
4 |
12
2 |
11
2 |
10
2 |
5
1 |
3
1 |
3
1 |
2
– |
–
– |
07 -____- 1601/6090 | A / B
C / D |
18
8 |
14
8 |
8
5 |
8
4 |
6
4 |
4
2 |
2
2 |
2
1 |
1
– |
–
– |
07 -____- 1601/6012 | A / B
C / D |
18
8 |
14
8 |
8
5 |
8
4 |
6
4 |
4
2 |
2
2 |
1
1 |
1
– |
–
– |
07 -____- 2601/6090 | A / B
C / D |
33
8 |
26
8 |
17
5 |
14
4 |
12
4 |
7
2 |
4
2 |
3
1 |
3
– |
–
– |
07 -____- 3601/6090 | A / B
C / D |
48
8 |
38
8 |
24
5 |
20
4 |
18
4 |
10
2 |
6
2 |
5 1 |
4
– |
–
– |
07 -____- 2552/5012 | A / B
C / D |
53
12 |
34
12 |
23
10 |
20
8 |
18
8 |
9
4 |
7
3 |
4
2 |
3
2 |
2
2 |
07 -____- 2552/5016 | A / B
C / D |
53
12 |
34
12 |
23
10 |
20
8 |
18
8 |
9
4 |
7
3 |
4
2 |
3
2 |
2
2 |
07 -____- 4002/5012 | A / B
C / D |
88
12 |
58
12 |
38
10 |
35
8 |
30
8 |
17
4 |
13
3 |
6
2 |
5
2 |
4
2 |
07 -____- 4002/5016 | A / B
C / D |
88
12 |
58
12 |
38
10 |
35
8 |
30
8 |
17
4 |
13
3 |
6
2 |
5
2 |
4
2 |
07 -____- 4004/0512 | A / B
C / D |
88
26 |
58
20 |
38
16 |
35
14 |
30
10 |
17
6 |
13
4 |
6
2 |
5
4 |
4
3 |
07 -____- 4004/0516 | A / B
C / D |
135
42 |
89
38 |
58
34 |
53
30 |
46
24 |
26
8 |
20
5 |
9
3 |
7
6 |
4
4 |
07 -____- 6002/5012 | A / B
C / D |
130
12 |
84
12 |
56
10 |
52
8 |
46
8 |
24
4 |
18
3 |
10
2 |
6
2 |
4
2 |
NOTE – if you wish another type of cable grommet to be used, please contact us.