Flameproof Transformer Station type IT3Su
The flameproof transformer station type IT3Su is designed to supply equipment with a rated voltage of 380 VAC to 1140 VAC and is suitable to supply frequency converters.
DESIGN:
The enclosure of the transformer station IT3Su consists of five flameproof compartments:
- connection compartment with cables or rubber cables supplying the transformer station;
- high voltage (HV) compartment housing switchgear;
- transformer compartment;
- low voltage (LV) compartment housing switchgear and protection equipment;
- connection compartment housing outgoing feeder rubber cables and control cables.
Transswitch type version:
- station can be delivered with more outgoing feeders on the low-voltage side,
- up to nine main outgoing feeders on the low-voltage side,
- possibility for installing auxiliary and control outgoing feeders,
- possibility for putting in main outgoing feeders in the form of retractable replaceable inserts,
- independent safety features for each main outgoing feeder.
Explosion protection
Explosion proof version
I M2 Ex db [ia ib] I Mb
I M2 Ex db [ia, ib, op is Ma] I Mb
PB Exd[iaib]I
PB Exd[iaib]sI
Certificate
TEST 13 ATEX 0075 X
TC BY/112 02.01. 103,0019
Rated values
Ingress protection rating
IP 54
Operating temperature
-10°C ≤ Ta ≤ +40°C
Rated power supply voltage
Un1 (HV) from 3×3000 VAC to 3×6300 VAC
Rated voltage of outgoing feeders
UN2 (LV) from 3×380 VAC to 3×1200 VAC
Rated power
From 400 kVA to 1800 kVA
Overall dimensions
From 3950x969x1470 mm (LxWxH)
To 5250x969x1470 mm (LxWxH)
Coding
I | T | 3 | S | u | * | ( | * | / | * | ) |
A | B | C |
A | Rated power in kVA |
B | Primary voltage in kV |
C | Secondary voltage in kV (in the case of a transformer with a second secondary winding or a switchable winding, two values are given) |