Intrinsically Safe Temperature Sensor type ICT

The intrinsically safe temperature sensor type ICTis used to measure the temperature of gases, liquids and solids in equipment, tanks, pressure piping etc.

This sensor can be used in hazardous areas at risk of gas and dust explosion classified in group I (methane, coal dust) and in group II. The device is equipped with an analogue output of 4-20 mA.

Iskrobezpieczny czujnik temperatury typu ICT

Explosion protection

Marking
I M1 Ex ia I Ma
II 1G Ex ia IIC T6/T5/T4 Ga

Ambient temperature
for group I-20°C to + 85°C
for group II-20°C to + 40°C for T6-20°C to + 50°C for T5-20°C to + 60°C for T4

Certificate

OBAC 06 ATEX 290X

Rated values

Ingress protection rating
IP65

Measuring element
Pt100

Connector thread
M20x1.5

Permissible pressure
1 MPa – standard version
3 MPa – special version

Installation length L
5 or 10 or 15 or 20 cm or other

Minimum depth of immersion in medium
25 mm

Outer thermowell material
acid-resistant steel 1H18N9

Maximum values of power supply circuit parameters, terminals 1 (+) and 2 (-)
Ui = 30 V DC
Ii = 100 mA
Pi = 750 mW

Internal inductance
negligible

Internal capacity
negligible

Sensor measuring circuit
Maximum electrical values to energise terminals 3, 4, 5, 6
Uo = 9.6 V DC
Io = 4.5 mA
Po = 11 mW

Maximum permissible value of internal inductance and capacitance
Lo = 4.5 MH/C0 = 709 NF – for IIb, IIC
Lo = 8.5 MH/C0 = 1300 NF – for IIb, IIC

Maximum probe length
500 mm

Coding